Direkt zum Inhalt
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + Hersteller

ICS-Advisories

Advisories speziell für industrielle Steuerungssysteme — von CISA ICS-CERT und direkt von Herstellern (darunter Siemens, ABB, Schneider Electric, WAGO und Phoenix Contact) — einschließlich Revisionshistorie (Erstveröffentlichung, Update A, Update B) und verknüpfter CVEs.

1

Gefunden

Advisory-Daten: Live-Anbindung— zuletzt abgerufen: 8. November 2026 um 10:21.

1 Advisories gefunden

2NGA003144

ABB AbilityTM zenon Security Risk Due to High-Severity Vulnerabilities in WIBU CodeMeter Runtime

ABB — AbilityTM zenon

ABB PSIRThoch

Veröffentlicht

9. September 2026

Letzte Aktualisierung

9. September 2026

Betroffene Sektoren

Risk Evaluation

ABB is aware of publicly disclosed security vulnerabilities affecting the WIBU-Systems CodeMeter Runtime for Windows, identified as CVE-2026-81572, CVE-2026-81573, CVE-2026-81574, CVE-2026-81575 and CVE-2026-81576. The CodeMeter Runtime component is used within affected ABB zenon Software Platform installations for software licensing and license server functionality. Successful exploitation of the reported vulnerabilities could enable local privilege escalation on Windows systems and impact systems configured as CodeMeter license servers, potentially leading to unauthorized access, service disruption, or loss of system integrity. Refer to the WIBU-Systems advisory for detailed technical information on each vulnerability. Please see the References section for the WIBU-Systems security advisory.

Zusammenfassung der Gegenmaßnahmen

ABB recommends the following mitigation measures: - Update the WIBU-Systems CodeMeter Runtime to version 8.41a or later. - The latest CodeMeter Runtime software is available from the WIBU-Systems download page: User Software - Wibu-Systems, please see the References section for the corresponding link. - Where upgrading is not feasible, ABB recommends that asset owners perform a risk assessment and implement compensating controls such as network isolation, access restrictions, and enhanced monitoring of affected systems. ABB recommends that customers apply the update at earliest convenience. The vulnerabilities associated with CVE-2026-81573, CVE-2026-81574, CVE-2026-81575 and CVE-2026-81576 are exploitable only when the WIBU-Systems CodeMeter Runtime is configured as a network server, which is not the de-fault configuration. The CVE-2026-81572 vulnerability requires local access to the affected Windows system and execution by a low-privileged user. Consequently, systems with restricted local access, proper privilege management, and limited network exposure are less likely to be successfully compromised. Refer to section “General security recommendations” for further advise on how to keep your system secure.

Revisionshistorie (1)
  1. Erstveröffentlichung — 9. September 2026

    Initial version.

Offizielle Quelle: ABB PSIRT