CISA + Hersteller
ICS-Advisories
Advisories speziell für industrielle Steuerungssysteme — von CISA ICS-CERT und direkt von Herstellern (darunter Siemens, ABB, Schneider Electric, WAGO und Phoenix Contact) — einschließlich Revisionshistorie (Erstveröffentlichung, Update A, Update B) und verknüpfter CVEs.
1
Gefunden
Advisory-Daten: Live-Anbindung— zuletzt abgerufen: 25. November 2026 um 00:34.
1 Advisories gefunden
7PAA025875DoS Vulnerability in System 800xA Batch Management - TCP Connection Resource ExhaustionABB · System 800xA Batch ManagementmiddelABB PSIRT1 CVE24. November 2026
Risk Evaluation
ABB is aware of a vulnerability affecting the versions of 800xA Batch Management listed as affected in the advisory. Under specific network conditions, a malicious user with access to the control network could cause temporary service degradation or a temporary denial of service. Successful exploitation may cause affected services to become temporarily unavailable. The affected service automatically resumes normal operation after malicious traffic is stopped and stale network connections are cleared by the operating system. Information disclosure, unauthorized code execution, and integrity impacts have not been observed.
Zusammenfassung der Gegenmaßnahmen
Workarounds are specific measures that a user can take to help block an attack, for example, temporarily disabling the vulnerable feature may remove the exposure with well-known impact on functionality. ABB has tested the following workarounds. Although these workarounds will not correct the underlying vulnerability, they can help block known attack vectors. When a workaround reduces functionality, this is identified below as “Impact of workaround”. ABB has identified the following workarounds that can reduce exposure: - Network Segmentation: Restrict access to systems running 800xA Batch Management through firewalls and industrial network segmentation. - Access Control: Allow TCP connections to port 40061/TCP only from authorized systems and trusted communication partners. - Monitoring: Monitor systems for abnormal connection volumes and investigate excessive TCP connection attempts. Impact of Workaround: No loss of system functionality is expected when standard industrial network security practices are implemented.
- Veröffentlicht
- 24. November 2026
- Letzte Aktualisierung
- 24. November 2026
- Verknüpfte CVEs
- CVE-2026-78354
- Betroffene Sektoren
- —
Revisionshistorie (2)
Erstveröffentlichung — 24. November 2026
Update in the Remediation Section.
Update A — 24. November 2026
Initial version.