Direkt zum Inhalt
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + Hersteller

ICS-Advisories

Advisories speziell für industrielle Steuerungssysteme — von CISA ICS-CERT und direkt von Herstellern (darunter Siemens, ABB, Schneider Electric, WAGO und Phoenix Contact) — einschließlich Revisionshistorie (Erstveröffentlichung, Update A, Update B) und verknüpfter CVEs.

1

Gefunden

Advisory-Daten: Live-Anbindung— zuletzt abgerufen: 7. November 2026 um 02:05.

1 Advisories gefunden

Advisory2025-08_VDE-2025-070

CODESYS Control V3 - NULL pointer dereference

CODESYS — CODESYS Control RTE (SL)

CODESYS PSIRThoch

Veröffentlicht

4. August 2025

Letzte Aktualisierung

14. Oktober 2025

Verknüpfte CVEs

Betroffene Sektoren

Risk Evaluation

A vulnerability in the CODESYS Control runtime system's CmpDevice component allows unauthenticated attackers to cause a denial-of-service (DoS) via specially crafted communication requests. The issue is triggered by a NULL pointer dereference and also affects systems when outdated CODESYS clients attempt to log in. Only PLCs based on the CODESYS Runtime Toolkit containing the components CmpDevice, CmpAuditLog, and CmpSessionInformation are impacted. **Update 1.1.0, 01.09.2025:** Updated remediation category - fixed SL runtimes are now available.

Zusammenfassung der Gegenmaßnahmen

The vulnerability can be mitigated by restricting the allowed login authentication type "CmpUserMgr/UserLogin_AuthenticationType" to "ONLY_ASYMMETRIC". This can be configured either via the Device Security Settings dialog in the CODESYS Development System or directly in the configuration file of the CODESYS Control runtime system (CODESYSControl.cfg) by adding the following setting: [CmpUserMgr] SECURITY.UserLogin_AuthenticationType=ONLY_ASYMMETRIC With this configuration in place, both potential attackers and legacy CODESYS protocol clients (prior to version 3.5.16.0) will be blocked from logging in, thereby preventing execution of the vulnerable code path.

Revisionshistorie (3)
  1. Erstveröffentlichung — 4. August 2025

    Initial revision.

  2. Update A — 1. September 2025

    Updated remediation category - fixed SL runtimes are now available.

  3. Update B — 14. Oktober 2025

    List of affected and fixed products corrected regarding CODESYS HMI (SL) and CODESYS Runtime Toolkit

Offizielle Quelle: CODESYS PSIRT