SEVD-2026-013-01

Multiple Third-Party Vulnerabilities on ProLeiT Plant iT/Brewmaxx

Schneider Electric — ProLeiT

Schneider Electric CPCERTkritisch

Veröffentlicht

13. Januar 2026

Letzte Aktualisierung

10. März 2026

Betroffene Sektoren

Risk Evaluation

Schneider Electric is aware of multiple vulnerabilities in Redis open-source database, affecting its Plant iT product. The [Plant iT/Brewmaxx](https://www.proleit.com/plant-it/) product is an object-oriented and PLC-based process control system with integrated Manufacturing Execution System functionality. The integrated and modular software platform consists of basic systems, modules and add-ons that can be flexibly combined. Failure to apply the remediations provided below may risk privilege escalation, which could result in remote code execution.

Zusammenfassung der Gegenmaßnahmen

Patch ProLeiT-2025-001 includes a fix to reduce the risk of exploit: • Install the patch to disable the eval commands in Redis on: o Application Server o VisuHub o Engineering Workstations o Workstation with emergency mode functionality • The patch ProLeiT-2025-001 is available via ProLeiT Support: https://www.proleit.com/support/ • Force usage of secure Redis configuration templates in system settings as documented in the patch manual. • Restart all patched Servers and Workstations

Revisionshistorie (2)
  1. Erstveröffentlichung — 13. Januar 2026

    Original Release

  2. Update A — 10. März 2026

    Updated the CWE description of CVE-2025-46819