Direkt zum Inhalt
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + Hersteller

ICS-Advisories

Advisories speziell für industrielle Steuerungssysteme — von CISA ICS-CERT und direkt von Herstellern (darunter Siemens, ABB, Schneider Electric, WAGO und Phoenix Contact) — einschließlich Revisionshistorie (Erstveröffentlichung, Update A, Update B) und verknüpfter CVEs.

1

Gefunden

Advisory-Daten: Live-Anbindung— zuletzt abgerufen: 7. November 2026 um 14:22.

1 Advisories gefunden

SSA-794185

SSA-794185: RADIUS Protocol Susceptible to Forgery Attacks (CVE-2024-3596) - Impact to SIPROTEC, SICAM and Related Products

Siemens — CPC80 Central Processing/Communication

Siemens ProductCERTkritisch

Veröffentlicht

13. Mai 2025

Letzte Aktualisierung

13. Oktober 2026

Verknüpfte CVEs

Betroffene Sektoren

Risk Evaluation

This advisory documents the impact of CVE-2024-3596 (also dubbed "Blastradius"), a vulnerability in the RADIUS protocol, to SIPROTEC, SICAM and related products. The vulnerability could allow on-path attackers, located between a Network Access Server (the RADIUS client, e.g., a SICAM device) and a RADIUS server, to forge Access-Request packets in a way that enables them to modify the corresponding server response packet at will, e.g., turning an "Access-Reject" message into an "Access-Accept". This would cause the Network Access Server to grant the attackers access to the network with the attackers desired authorization (and without the need of knowing or guessing legitimate access credentials). Further details incl. external references can be found in the chapter "Additional Information". Siemens has released new versions for several affected products and recommends to update to the latest versions, and to configure the updated systems as recommended in the chapter "Additional Information". Siemens has released new versions for the affected products and recommends to update to the latest versions.See chapter "Additional Information" for details.

Zusammenfassung der Gegenmaßnahmen

Configure the RADIUS server to require the presence of a Message-Authenticator attribute in all Access-Request packets from RADIUS client devices that support it

Revisionshistorie (4)
  1. Erstveröffentlichung — 13. Mai 2025

    Publication Date

  2. Update A — 12. August 2025

    Added fix for affected firmware modules in SICAM A8000 (CPCI85 for CP-8031/CP-8050, CPC80 for CP-8000/CP-8021/CP-8022, SICORE for CP-8010/CP-8012), SICAM EGS (CPCI85) and SICAM S8000 (SICORE). Added fix for SICAM Q200, for SIPROTEC 5 - CP300 and CP150 Devices, and for SIPROTEC 5 Compact 7SX800 (CP050). Added SICAM AK 3, SICAM BC, SICAM TM, SICAM GridEdge and SIPROTEC 5 - CP200 Devices to the list of known not affected products

  3. Update B — 11. November 2025

    Added fix for SIPROTEC 5 - CP100 Devices

  4. Update C — 9. Juni 2026

    Added fix for PowerLink IP

Offizielle Quelle: Siemens ProductCERT