CISA + Hersteller
ICS-Advisories
Advisories speziell für industrielle Steuerungssysteme — von CISA ICS-CERT und direkt von Herstellern (darunter Siemens, ABB, Schneider Electric, WAGO und Phoenix Contact) — einschließlich Revisionshistorie (Erstveröffentlichung, Update A, Update B) und verknüpfter CVEs.
1
Gefunden
Advisory-Daten: Live-Anbindung— zuletzt abgerufen: 7. November 2026 um 03:37.
Filter
1 aktiv1 Advisories gefunden
VDE-2022-030
Lenze: Vulnerability in the OPC-UA authentification connection in the firmware
Veröffentlicht
11. Juli 2022
Letzte Aktualisierung
11. Juli 2022
Verknüpfte CVEs
Betroffene Sektoren
Risk Evaluation
The machine controller of the cabinet series include an OPC-UA server which uses an user management to authenticate clients via anonymous or user/password authentication. If the user/password authentication is selected, password verification is skipped upon second login. As a result, cases occur in which users can establish communication without correct authentication. This vulnerability is not located in the OPC-UA protocol or server, but in the interface to the products firmware. This Security Advisory is only relevant for the following use cases: • the user management has been activated on the machine controller (is deactivated by default) • the OPC-UA Server is used • Data are transferred via a symbol configuration (is not available by default)
Zusammenfassung der Gegenmaßnahmen
As part of a security strategy, Lenze SE recommends the following general defense measures to reduce the risk of exploits: • Only use the products in a protected and controlled environment to minimize network impact and to ensure that they are inaccessible from outside. • Use external firewalls to protect the automation system network and to separate it from other networks. Remark: One Measure should be to block port 4840 via the external firewall and open this port for authenticated access only. • Use Virtual Private Networks (VPN) tunnels when remote access is required. • Use IDS (Intrusion Detection Systems) where possible to detect anomalies in the network. • Activate and use user administration and password functions. • Use encrypted communication links. • Restrict access to both the development tools and their projects and the products of the automation system by physical means, operating system functions, etc. • Protect the development tool by using the latest virus detection solutions. • Use of certificate-based communication via the message security modes Sign or Sign&Encrypt and trust of the corresponding client certificates on the machine controller by the OPC-UA server. This can reduce the risk of exploiting this vulnerability.
Revisionshistorie (1)
Erstveröffentlichung — 11. Juli 2022
Initial revision.