Direkt zum Inhalt
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + Hersteller

ICS-Advisories

Advisories speziell für industrielle Steuerungssysteme — von CISA ICS-CERT und direkt von Herstellern (darunter Siemens, ABB, Schneider Electric, WAGO und Phoenix Contact) — einschließlich Revisionshistorie (Erstveröffentlichung, Update A, Update B) und verknüpfter CVEs.

1

Gefunden

Advisory-Daten: Live-Anbindung— zuletzt abgerufen: 7. November 2026 um 14:22.

1 Advisories gefunden

VDE-2024-013

HIMA: Multiple products affected by DoS and Port-Based-VLAN Crossing

HIMA — F30 03X YY (COM) all variants

HIMA PSIRThoch

Veröffentlicht

13. Februar 2024

Letzte Aktualisierung

22. Mai 2025

Betroffene Sektoren

Risk Evaluation

CVE-2024-24781: If the above mentioned products are loaded with Wire speed (1Gbit/s or 100Mbit/s) the resources of the Ethernet-Controller are exhausted and it must be reset by the system automatically after load disappears. This leads to an interruption (DoS) of all other communications of the affected Ethernet-Controller. CVE-2024-24782: Most of the above mentioned products offer a VLAN feature. This helps to segregate ports of the switch included in each of the products. VLAN are meant to segregate networks. Furthermore a MAC-learning mode called 'conservative' is provided. In this mode the ARP table is updated earliest within 1..2 times ARP aging time. X-SB 01 (985210207) is not affected by this CVE.

Zusammenfassung der Gegenmaßnahmen

CVE-2024-24781: All load limiting measures are helpful (e.g. in external devices or also in the switch of the above mentioned products). Please check whether the reduced speed is still sufficient for the desired application. Protect the network with segregation measures and restrict the access of unauthorized network participants (e.g. close unused ports) CVE-2024-24782: Switching the MAC-learning from 'conservative' to 'tolerant' mitigates the above described vulnerability but leads to potential IP-Spoofing and ARP-Poisoning and should therefore be avoided. HIMax and HIQuad X systems can be setup in the way that real physical segregation (between different modules) is used. E.g. it is impossible to ping from one X-COM to another X-COM in the same Rack. HIMatrix should be used in that way that CPU and COM are NOT connected via VLAN e.g. CPU connected to Port 1 and 2, COM Connected to Port 3 and 4.

Revisionshistorie (2)
  1. Erstveröffentlichung — 13. Februar 2024

    Initial revision.

  2. Update A — 22. Mai 2025

    Fix: quotation mark

Offizielle Quelle: HIMA PSIRT