1 Advisories gefunden

VDE-2024-048

Beckhoff: Improper neutralization of input in IPC-Diagnostics-www package included in TwinCAT/BSD operating system

Beckhoff — IPC-Diagnostics-www package

Beckhoff PSIRThoch

Veröffentlicht

27. August 2024

Letzte Aktualisierung

22. Mai 2025

Verknüpfte CVEs

Betroffene Sektoren

Risk Evaluation

By default, TwinCAT/BSD-based products have a device-specific web interface for web-based management (WBM) enabled, developed by Beckhoff and known as Beckhoff Device Manager UI. It can be accessed remotely or locally. When accessed locally, the user can bypass input validation by entering specially crafted inputs into the user interface for certain pages, which then allows local commands to be executed with administrative privileges.

Zusammenfassung der Gegenmaßnahmen

Avoid the existence of user accounts with login permission on the target other than administrator access. By default, TwinCAT/BSD has preconfigured user accounts with lower privileges, but none of them have a password, which results in them being denied login access. Avoid running third-party applications on the target that have not been properly audited, regardless of the user they are running as.

Revisionshistorie (4)
  1. Erstveröffentlichung — 13. August 2024

    initial revision

  2. Update A — 6. November 2024

    Fix: correct certvde domain, added self-reference

  3. Update B — 16. Januar 2025

    Fix: list of branches

  4. Update C — 11. April 2025

    Fix: version range

Offizielle Quelle: Beckhoff PSIRT