Direkt zum Inhalt
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + Hersteller

ICS-Advisories

Advisories speziell für industrielle Steuerungssysteme — von CISA ICS-CERT und direkt von Herstellern (darunter Siemens, ABB, Schneider Electric, WAGO und Phoenix Contact) — einschließlich Revisionshistorie (Erstveröffentlichung, Update A, Update B) und verknüpfter CVEs.

1

Gefunden

Advisory-Daten: Live-Anbindung— zuletzt abgerufen: 7. November 2026 um 14:22.

1 Advisories gefunden

VDE-2025-075

Beckhoff: Deserialization of untrusted data by TwinCAT 3 Engineering

Beckhoff — TE1000 | TwinCAT 3 Enineering

Beckhoff PSIRThoch

Veröffentlicht

9. September 2025

Letzte Aktualisierung

9. September 2025

Verknüpfte CVEs

Betroffene Sektoren

Risk Evaluation

Beckhoff's TwinCAT 3 Engineering software is intented to craft automation projects consisting of a set of files which are stored locally as files underneath an individual folder or in a packed file. The TwinCAT 3 Engineering stores user settings and preferences among the non packed local files which are relevant to continue former work on the project conventienly. TwinCAT 3 Engineering stores such settings in files which are called "Solution User Options (.suo) File". When such settings are manipulated or crafted by an adversary in a specific way then TwinCAT 3 Engineering executes arbitrary commands as determined by these settings when the user uses TwinCAT 3 Engineering to open the project. These arbitrary commands are executed in the user context. Please note that solution user option files should not be checked in to source code control. This is also a best practice when working with source code projects and solutions. For example, see https://learn.microsoft.com/en-us/visualstudio/extensibility/internals/solution-user-options-dot-suo-file and https://infosys.beckhoff.com/content/1033/tc3_sourcecontrol/14604066827.html. The vulnerability is similar to older vulnerabilities that were addressed in the CODESYS Development System V3 product from CODESYS GmbH with CVE-2021-21864, CVE-2021-21865, CVE-2021-21866, CVE-2021-21867, CVE-2021-21868, CVE-2021-21869, and the associated Advisory 2021-13 from CODESYS GmbH.

Zusammenfassung der Gegenmaßnahmen

Please update to a recent version of the affected product and uninstall older versions of TwinCAT 3 Engineering. Make sure that older versions of TwinCAT 3 Engineering do not occur as "Remote Manager" versions, see https://infosys.beckhoff.com/content/1033/tc3_remote_manager/index.html?id=1584127271344589360. Remove the "pinning" from your projects to older versions of TwinCAT 3 Engineering, if present, see https://infosys.beckhoff.com/content/1033/tc3_remote_manager/3154642571.html.

Revisionshistorie (1)
  1. Erstveröffentlichung — 9. September 2025

    initial revision

Offizielle Quelle: Beckhoff PSIRT