CVE-2026-34223
A vulnerability has been identified in Desigo CC ClickOnce Client V6 (All versions), Desigo CC ClickOnce Client V7 (All versions), Desigo CC family V8 (All versions), Desigo CC family V9 (All versions), Desigo CC Flex Client V6 (All versions), Desigo CC Flex Client V7 (All versions), Desigo CC Installed Client V6 (All versions), Desigo CC Installed Client V7 (All versions). The affected application is vulnerable to Client Code Execution (CCE) due to insufficient input validation when handling scripts embedded within user-defined graphics documents. Specifically, when the script within a graphics document is designed or modified by an attacker to include malicious commands. When a user opens a compromised graphics document, the embedded script is executed on the client application instance, allowing an attacker to write arbitrary files to the client's operating system. Successful exploitation requires an attacker to craft a malicious graphics document and entice a user with sufficient privileges to display it. This could lead to compromise of the client operating system and potential lateral movement within the organization.
Dieser Datensatz: Live-Anbindung— zuletzt abgerufen: 24. September 2026 um 05:08.
Direkt aus NVD, CISA oder vom Hersteller übernommen — teils auf Englisch, unverändert gegenüber der Quelle.
A vulnerability has been identified in Desigo CC ClickOnce Client V6 (All versions), Desigo CC ClickOnce Client V7 (All versions), Desigo CC family V8 (All versions), Desigo CC family V9 (All versions), Desigo CC Flex Client V6 (All versions), Desigo CC Flex Client V7 (All versions), Desigo CC Installed Client V6 (All versions), Desigo CC Installed Client V7 (All versions). The affected application is vulnerable to Client Code Execution (CCE) due to insufficient input validation when handling scripts embedded within user-defined graphics documents. Specifically, when the script within a graphics document is designed or modified by an attacker to include malicious commands. When a user opens a compromised graphics document, the embedded script is executed on the client application instance, allowing an attacker to write arbitrary files to the client's operating system. Successful exploitation requires an attacker to craft a malicious graphics document and entice a user with sufficient privileges to display it. This could lead to compromise of the client operating system and potential lateral movement within the organization.
CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:H
Attack Vector
LOCAL
Privileges Required
LOW
User Interaction
REQUIRED
Vertraulichkeit
Hoch
Integrität
Hoch
Verfügbarkeit
Hoch
Ausnutzungswahrscheinlichkeit innerhalb von 30 Tagen
0.1%
Perzentil
3e
Quelle: FIRST.org, aktualisiert am 23. September 2026.
Evaluate authorization policy for Graphics application following Least Privilege principle, so only required users have access to the configuration.
Unsere eigene Einordnung und unser Kontext zu den obigen Quelldaten.
IACS-Radar-Einordnung
Unsere eigene Einordnung und unser Kontext zu dieser Schwachstelle — keine offizielle Quelle.
IACS-Radar-Prioritätswert
Basierend auf CVSS 8.2, EPSS 0.1%, industrielle Relevanz 55/100.
Kombiniert CVSS, EPSS, KEV-Status, industrielle Relevanz und Expositionsrelevanz — eine Ergänzung, kein Ersatz für die einzelnen Werte darunter und darüber.
Voraussetzungen für eine Ausnutzung
Operative Auswirkungen & Energierelevanz
Möglicher Verlust der Sicht auf oder der Kontrolle über den Prozess bei erfolgreicher Ausnutzung.
Als relevant für den Energiesektor eingestuft aufgrund von: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Der Hersteller „Siemens“ ist ein bekannter Lieferant von Ausrüstung für den Energiesektor.
Empfohlene defensive Maßnahmen
Industrieller Relevanzwert
Die Einstufung ist vorläufig; eine manuelle Überprüfung durch einen OT-Security-Analysten wird empfohlen.
Klassifiziert von IACS Radar-analysepijplijn (geautomatiseerd) am 24. September 2026.
IEC-62443-Zuordnung