Skip to content
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + vendors

ICS Advisories

Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.

1

Found

Advisory data: live connection— last retrieved: 7 November 2026 at 02:05.

Filters

1 active
Reset filters

1 advisories found

Advisory2026-03_VDE-2026-018

CODESYS Control V3 - Externally-controlled format string in Auditlog

CODESYS — CODESYS Control RTE (SL)

CODESYS PSIRThigh

Published

24 March 2026

Last update

18 June 2026

Linked CVEs

Affected sectors

Risk evaluation

The CODESYS Control runtime system's CmpAuditLog component allows potentially unauthenticated remote attackers to control the format string of processed log messages. Due to the internal processing logic, the impact is limited to a crash of the CODESYS Control runtime.

Mitigation summary

As a mitigation, the Audit Log feature can be disabled in the CODESYS Control runtime configuration file. When the Audit Log logger is not enabled, the affected functionality is no longer exposed and the vulnerability cannot be exploited. To disable the Audit Log feature, use the following settings. Depending on your existing configuration, the logger index may vary. [CmpLog] Logger.0.Name=.Audit.log Logger.0.Enable=0

Revision history (2)
  1. Initial publication — 24 March 2026

    Initial revision.

  2. Update A — 18 June 2026

    Updated remediation category - fixed SL runtimes are now available. Updated mitigation category - clarified description.

Official source: CODESYS PSIRT