Skip to content
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + vendors

ICS Advisories

Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.

1

Found

Advisory data: live connection— last retrieved: 7 November 2026 at 01:34.

Filters

1 active
Reset filters

1 advisories found

Advisory2026-08_VDE-2026-056

CODESYS Control - Incorrect Authorization

CODESYS — CODESYS Control RTE (SL)

CODESYS PSIRThigh

Published

26 May 2026

Last update

18 June 2026

Linked CVEs

Affected sectors

Risk evaluation

The CODESYS Control runtime system provides a user management mechanism with multiple privilege groups including the visualization administrators group, which is intended solely to manage visualization users. Due to insufficient authorization checks an authenticated remote user with low-privileged visualization administrator access can delete higher-privileged accounts. However, independent mechanisms protect the deletion of the last remaining device admin user, preventing a complete loss of administrative access to the device. The CODESYS Control runtime system is only affected if the optional visualization user management feature is enabled and a visualization administrator account has been configured.

Mitigation summary

Update the following products to version 3.5.22.20. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS HMI (SL) * CODESYS Runtime Toolkit The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.

Revision history (2)
  1. Initial publication — 26 May 2026

    Initial revision.

  2. Update A — 18 June 2026

    Updated remediation category - fixed SL runtimes are now available.

Official source: CODESYS PSIRT