CISA + vendors
ICS Advisories
Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.
1
Found
Advisory data: live connection— last retrieved: 7 November 2026 at 02:05.
Filters
1 active1 advisories found
Risk evaluation
The CmpWebServer component in the CODESYS Control Runtime allows users to create browser-based visualizations for monitoring and controlling industrial processes. Due to improper bounds checking, a specially crafted HTTP request from an unauthenticated remote attacker may lead to a size-limited out-of-bounds write, causing a denial of service of the affected device. The CODESYS Control runtime system is only affected if the web server is active, which by default requires a running application with an enabled Web Visualization.
Mitigation summary
Update the following products to version 3.5.22.20. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS HMI (SL) * CODESYS Runtime Toolkit The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.
Revision history (2)
Initial publication — 26 May 2026
Initial revision.
Update A — 18 June 2026
Updated remediation category - fixed SL runtimes are now available.