Advisory2026-11_VDE-2026-094

CODESYS Gateway Client - Uncontrolled Memory Allocation

CODESYS — CODESYS Development System 3

CODESYS PSIRThigh

Published

30 September 2026

Last update

22 October 2026

Linked CVEs

Affected sectors

Risk evaluation

The CODESYS Gateway Client (CmpGwClient) is used by various CODESYS products to establish PLC communication via the CODESYS Gateway. Due to missing limits on memory allocations derived from a size field in a gateway response, a malicious gateway can cause excessive memory consumption in the client, resulting in a denial-of-service condition. The vulnerability can be exploited when an affected product connects to an attacker-controlled gateway.

Mitigation summary

Update the following products to version 3.5.22.40. * CODESYS Development System 3 * CODESYS Gateway * CODESYS Edge Gateway for Windows * CODESYS HMI (SL) * CODESYS OPC DA Server SL * CODESYS PLCHandler * CODESYS Runtime Toolkit The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.

Revision history (2)
  1. Initial publication — 30 September 2026

    Initial revision.

  2. Update A — 22 October 2026

    Updated remediation category - fixed SL runtimes are now available, updated summary - typo corrected, formal adaptions.

Official source: CODESYS PSIRT