CISA + vendors
ICS Advisories
Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.
1
Found
Advisory data: live connection— last retrieved: 7 November 2026 at 02:05.
Filters
1 active1 advisories found
Risk evaluation
A vulnerability in the Wibu CodeMeter Runtime, which is part of the installation packages of several Festo products, was found. An attacker exploiting the vulnerability in WIBU CodeMeter Runtime in server mode could gain full access to the affected server via network access without any user interaction. This could lead to remote code execution and escalation of privileges giving full admin access on the host system for an already authenticated user (logged in locally to the PC).
Mitigation summary
Update CodeMeter Runtime to version >= 7.60c The latest version of CodeMeter Runtime can be downloaded from WIBU System's web site.
Revision history (3)
Initial publication — 28 November 2023
Initial version
Update A — 5 December 2023
Removed 'MES4 (v3)', 'MES4 (<=v2)' and 'Energy-PC' from affected products as they do not install WIBU CodeMeter Runtime.
Update B — 13 May 2025
Adjusted to VDE template and updated information on fixed version of the Festo Automation Suite. Changed document title from 'Vulnerable Wibu CodeMeter Runtime in Several Festo Products' to 'Festo: Vulnerable WIBU-SYSTEMS CodeMeter Runtime in several products'. Updated legal disclaimer to add references to special provisions.