FSA-202406
Several Codesys Gateway v2 vulnerabilities in Codesys provided by Festo
Published
3 December 2024
Last update
3 December 2024
Linked CVEs
Affected sectors
Risk evaluation
An unauthenticated attacker would be able to send crafted requests to cause the CODESYS Gateway Server V2 to allocate excessive memory or consume all available TCP client connections. Besides, passwords are insufficiently checked during login. All versions of the following CODESYS V2 product prior version V2.3.9.38 are affected: • CODESYS Gateway Server
Mitigation summary
Enable password protection at login in case no password is set at the controller. Please note that the password configuration file is not covered by the default FFT backup and restore mechanism. You must select the related file manually.
Revision history (2)
Initial publication — 3 December 2024
Initial version
Update A — 3 December 2024
One reference has been corrected