CISA + vendors
ICS Advisories
Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.
1
Found
Advisory data: live connection— last retrieved: 8 November 2026 at 08:48.
Filters
1 active1 advisories found
Risk evaluation
A vulnerability in Desigo DXR and PXC controllers has been identified that could allow an attacker to cause denial of service conditions by sending malformed BACnet packets. Recovery requires a device reset or reboot to restore normal functionality. Siemens has released new versions for the affected products and recommends to update to the latest versions.
Mitigation summary
Update to V01.21.233.16-7862 or later version Please contact your local Siemens office for additional support in obtaining the update.
Revision history (2)
Initial publication — 11 August 2026
Publication Date
Update A — 13 August 2026
Initial CISA Republication of Siemens SSA-781903 advisory