SA25P003
B&R Automation Runtime Vulnerabilities in System Diagnostic Manager (SDM)
Published
7 October 2025
Last update
14 May 2026
Linked CVEs
Affected sectors
Energieopwekking
Risk evaluation
An update is available that resolves a vulnerability identified by B&Rs internal security analysis in the product versions listed as affected in this advisory. An attacker who successfully exploited these vulnerabilities could take over a remote session or execute code in the context of the user’s browser session.
Mitigation summary
The problem is corrected in Automation Runtime 6.4. The System Diagnostic Manager (SDM) is disabled by default in Automation Runtime 6 and is not intended be enabled on active systems located outside properly secured production networks or in facilities lacking adequate physical and logical access controls to prevent any form of unauthorized interaction. For customers who use SDM on their systems, B&R recommends applying the update based on risk assessment at the earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual.
Revision history (3)
Initial publication — 7 October 2025
Initial version.
Update A — 14 October 2025
Added information about CVE-2025-11498.
Update B — 14 May 2026
Corrected vendor name from 'ABB' to 'B&R Industrial Automation GmbH' to ensure accurate product matching.