CISA + vendors
ICS Advisories
Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.
1
Found
Advisory data: live connection— last retrieved: 7 November 2026 at 03:37.
Filters
1 active1 advisories found
VDE-2020-028
WAGO: Authentication Bypass Vulnerability in WAGO 750-36X and WAGO 750-8XX Version <= FW03
Risk evaluation
The Web-Based Management (WBM) of WAGOs programmable logic controller (PLC) is typically used for administration, commissioning and updates. With special crafted requests it is possible to change some special parameters without authentication.
Mitigation summary
* Restrict network access to the device. * Do not directly connect the device to the internet. * Disable unused TCP/UDP ports. * Disable web-based management ports 80/443 after the configuration phase
Revision history (3)
Initial publication — 30 September 2020
initial revision
Update A — 10 April 2025
Fixed csaf reference URL
Update B — 14 May 2025
Fix: added distribution