VDE-2024-045
Beckhoff: Local authentication bypass in IPC-Diagnostics package included in TwinCAT/BSD operating system
Risk evaluation
By default, TwinCAT/BSD-based products have a device-specific web interface for web-based management (WBM) enabled, developed by Beckhoff and known as Beckhoff Device Manager UI. It can be accessed remotely or locally. When accessed locally, the authentication mechanism for the web interface can be bypassed by any local user, regardless of their permissions, and they can act with administrative access rights via this mechanism.
Mitigation summary
Avoid the existence of user accounts with login permission on the target other than administrator access. By default, TwinCAT/BSD has preconfigured user accounts with lower privileges, but none of them have a password, which results in them being denied login access. Avoid running third-party applications on the target that have not been properly audited, regardless of the user they are running as.
Revision history (4)
Initial publication — 13 August 2024
initial revision
Update A — 6 November 2024
Fix: correct certvde domain, added self-reference
Update B — 16 January 2025
Fix: list of branches, references url
Update C — 11 April 2025
Fix: version range