Skip to content
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + vendors

ICS Advisories

Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.

1

Found

Advisory data: live connection— last retrieved: 7 November 2026 at 15:23.

Filters

1 active
Reset filters

1 advisories found

VDE-2024-050

Beckhoff: Denial-of-Service vulnerability in the MDP package included in TwinCAT/BSD operating system

Beckhoff — MDP package version

Beckhoff PSIRTmiddel

Published

27 August 2024

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

By default, TwinCAT/BSD-based products have a device-specific web interface for web-based management (WBM) enabled, developed by Beckhoff and known as Beckhoff Device Manager UI. It can be accessed remotely or locally. When accessed locally, a user can post specifically crafted input which then causes a buffer overflow on stack which in turn lets the process 'MDPService' crash such that the web interface becomes unavailable until next restart or even execute code in the context of user 'root'.

Mitigation summary

Avoid the existence of user accounts with login permission on the target other than administrator access. By default, TwinCAT/BSD has preconfigured user accounts with lower privileges, but none of them have a password, which results in them being denied login access. Avoid running third-party applications on the target that have not been properly audited, regardless of the user they are running as.

Revision history (4)
  1. Initial publication — 13 August 2024

    initial revision

  2. Update A — 6 November 2024

    Fix: correct certvde domain, added self-reference

  3. Update B — 16 January 2025

    Fix: list of branches, typo in reference url

  4. Update C — 11 April 2025

    Fix: version range

Official source: Beckhoff PSIRT