ICS Advisories
Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.
1
Found
Advisory data: live connection— last retrieved: 7 November 2026 at 01:04.
Filters
1 active1 advisories found
Risk evaluation
Several WAGO Firmwares are vulnerable, due to an incorrect calculation of the buffer size in the CODESYS OPC UA STACK. This can lead to a crash of the runtime of the following firmware versions installed on several devices.
Mitigation summary
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
Revision history (1)
Initial publication — 4 February 2025
Initial release.