VDE-2025-011
PEPPERL+FUCHS: Profinet Gateway LB8122A.1.EL – Device is affected by XSS vulnerability and information disclosure
Published
26 May 2025
Last update
27 August 2025
Linked CVEs
Affected sectors
Risk evaluation
A stored cross-site scripting vulnerability has been discovered in the profinet gateway LB8122A.1.EL. An attacker can write an HTML tag with up to 32 characters in the message field of a HART transmitter. The HTML tag is interpreted as HTML when the HART information is displayed in a webbrowser. If the HTML tag contains a link to a manipulated page, a user can be tricked into accessing this page. Furthermore, an attacker can access information about running processes via the SNMP protocol. Sending such SNMP read commands can also trigger a reboot.
Mitigation summary
Please install the updated firmware V1.3.13.
Revision history (2)
Initial publication — 5 June 2025
Initial revision.
Update A — 27 August 2025
Update: CWE from CVE-2025-41654, Revision History