CISA + vendors
ICS Advisories
Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.
1
Found
Advisory data: live connection— last retrieved: 7 November 2026 at 01:04.
Filters
1 active1 advisories found
Risk evaluation
The vulnerability in the Ethernet switch circuit is caused by a PullUp resistor at the reset input, leading to premature activation and undefined operation. Switching to a PullDown resistor keeps the switch in reset. This issue affects the CC100, the Touch Panels 600 and the Edge Controller.
Mitigation summary
To address this vulnerability, it is recommended to utilize a newer hardware revision equipped with Firmware 04.08.05 (FW30). This firmware version is designed to resolve the issue by properly managing the switch activation and configuration process on the revised hardware. It is important to note that older firmware versions will not resolve the problem on the new hardware revision, and therefore upgrading both the hardware and firmware is necessary for an effective remediation.
Revision history (1)
Initial publication — 15 September 2025
Initial revision.