Risk evaluation
Multiple WAGO devices are affected by a vulnerability in the dynamic creation of BACnet File Objects. The object name is used as a file path without sufficient validation and is not restricted to the intended directory, so relative paths can be used to reach files elsewhere in the file system.
Mitigation summary
Update to Firmware version 4.8.9 (FW30) or higher. For the latest custom Firmware please contact the WAGO support.
Revision history (1)
Initial publication — 1 October 2026