CISA + vendors
ICS Advisories
Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.
1
Found
Advisory data: live connection— last retrieved: 7 November 2026 at 14:22.
Filters
1 active1 advisories found
Risk evaluation
A vulnerability in the REST API of the JUMO device allows an attacker to trigger a denial‑of‑service (DoS) condition. Due to an incorrect implementation of the arrayLimit option in the Node.js qs module, limits for incoming request parameters are not properly enforced. As a result, an attacker can send specially crafted requests containing excessively large or deeply nested arrays, causing the web server to become unresponsive. This condition leads to a crash of the web server, followed by an automatic restart of the device.
Mitigation summary
Update the affected products to version 431.10.0.0.26 for variTRON 300, to version 388.10.0.0.26 for variTRON 500 and to version 446.10.0.0.26 for variTRON 500 touch. The release of this versions are expected to Q2 2026.
Revision history (1)
Initial publication — 26 May 2026
Release version.