Skip to content
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + vendors

ICS Advisories

Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.

1

Found

Advisory data: live connection— last retrieved: 7 November 2026 at 00:32.

Filters

1 active
Reset filters

1 advisories found

VDE-2026-127

Welotec: PHP2Shell Vulnerabilities in SMART EMS

Welotec — SmartEMS

Welotec PSIRTcritical

Published

29 October 2026

Last update

29 October 2026

Affected sectors

Risk evaluation

Two memory-safety vulnerabilities in the PHP runtime bundled with SMART EMS allow an unauthenticated remote attacker to execute arbitrary code in the context of the PHP web worker. All SMART EMS versions up to and including v3.5.3 are affected. Exploitability and reliability depend on the PHP server interface, configuration, application behaviour, and worker reuse.

Mitigation summary

Do not expose the SMART EMS Web UI directly to the internet or other untrusted networks. Restrict access to trusted administrator workstations through network segmentation, firewall rules, or a VPN. Where operationally possible, enforce `memory_limit=-1` administratively and restart all PHP workers. Use a container or cgroup memory limit as an availability boundary and enforce conservative request-size, input, multipart-part, header, and nesting limits at the frontend. If multipart form data is not required, block such requests before they reach PHP. These measures reduce exposure to confirmed attack paths but are not a complete mitigation.

Revision history (1)
  1. Initial publication — 29 October 2026

    Initial release.

Official source: Welotec PSIRT