CVE-2020-12495
Endress+Hauser Ecograph T (Neutral/Private Label) (RSG35, ORSG35) with Firmware version prior to V2.0.0 is prone to improper privilege management. The affected device has a web-based user interface with a role-based access system. Users with different roles have different write and read privileges. The access system is based on dynamic "tokens". The vulnerability is that user sessions are not closed correctly and a user with fewer rights is assigned the higher rights when he logs on.
This record: live connection— last retrieved: 7 November 2026 at 02:35.
Vendor
Published
19 November 2020
Last modified
17 June 2026
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
Endress+Hauser Ecograph T (Neutral/Private Label) (RSG35, ORSG35) with Firmware version prior to V2.0.0 is prone to improper privilege management. The affected device has a web-based user interface with a role-based access system. Users with different roles have different write and read privileges. The access system is based on dynamic "tokens". The vulnerability is that user sessions are not closed correctly and a user with fewer rights is assigned the higher rights when he logs on.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
None
Integrity
High
Availability
High
Probability of exploitation within 30 days
0.9%
Percentile
60e
Source: FIRST.org, updated on 6 November 2026.
Customers should configure a perimeter firewall to block traffic from untrusted networks and users to the device. These recommendations will be incorporated into the device documentation (operating instructions). Change default password for operator, service and admin account. Endress+Hauser will not change this behavior. Customers are recommended to take the measures for Temporary Fix / Mitigation as described above.
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 9.1, EPSS 0.9%, industrial relevance 40/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Possible loss of visibility of or control over the process upon successful exploitation.
No strong energy-sector-specific signals recognised; general OT/ICS relevance.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 7 November 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.