CVE-2025-41738
An unauthenticated remote attacker may cause the visualisation server of the CODESYS Control runtime system to access a resource with a pointer of wrong type, potentially leading to a denial-of-service (DoS) condition.
This record: live connection— last retrieved: 7 November 2026 at 00:02.
Products
AC500 V3 Firmware, CC100, PFC100, PFC200, TP600, Edge Controller and 13 more
up to version <3.9.1
Published
1 December 2025
Last modified
17 June 2026
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
An unauthenticated remote attacker may cause the visualisation server of the CODESYS Control runtime system to access a resource with a pointer of wrong type, potentially leading to a denial-of-service (DoS) condition.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
None
Integrity
None
Availability
High
Probability of exploitation within 30 days
0.4%
Percentile
36e
Source: FIRST.org, updated on 5 November 2026.
The problem is corrected in the following product version: - AC500 V3 firmware version 3.9.1 ABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and integrated into Automation Builder 2.9.1. Automation Builder 2.9.1 is available for download from the related download site. https://www.abb.com/global/en/areas/motion/digital-tools/automation-builder/software-download
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 7.5, EPSS 0.4%, industrial relevance 55/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Possible loss of visibility of or control over the process upon successful exploitation.
Assessed as relevant to the energy sector based on: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Vendor "ABB" is a known supplier of equipment for the energy sector.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 7 November 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.