CVE-2026-35226
An out‑of‑bounds write vulnerability in the CODESYS PROFINET Controller allows an unauthenticated attacker on the same network segment to send malformed PROFINET communication data that triggers an exception in the affected PLC application. The exception is handled by the CODESYS Control runtime system and results in a controlled stop of the PLC application.
This record: live connection— last retrieved: 7 November 2026 at 01:34.
Vendor
Published
29 July 2026
Last modified
24 October 2026
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
An out‑of‑bounds write vulnerability in the CODESYS PROFINET Controller allows an unauthenticated attacker on the same network segment to send malformed PROFINET communication data that triggers an exception in the affected PLC application. The exception is handled by the CODESYS Control runtime system and results in a controlled stop of the PLC application.
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
None
Integrity
None
Availability
High
Probability of exploitation within 30 days
0.3%
Percentile
21e
Source: FIRST.org, updated on 6 November 2026.
Update the following product to version 4.8.0.0. * CODESYS PROFINET To make the fix effective for existing CODESYS projects, you must additionally update the PROFINET Controller in the device tree to the latest version and perform a download of the CODESYS application to the PLC. The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 6.5, EPSS 0.3%, industrial relevance 65/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Possible loss of visibility of or control over the process upon successful exploitation.
Assessed as relevant to the energy sector based on: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Productbeschrijving komt overeen met de categorie "PLC", een typisch OT/ICS-componenttype. Description mentions industrial protocol: profinet.
Recommended defensive measures
Industrial relevance score
Automatically classified as industrially relevant based on CISA/NVD signals (see reasons).
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 7 November 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.