Loading vulnerabilities…
Loading vulnerabilities…
CVE-2026-61884
The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.
This record: live connection— last retrieved: 24 September 2026 at 05:10.
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
High
Integrity
High
Availability
High
Probability of exploitation within 30 days
0.4%
Percentile
38e
Source: FIRST.org, updated on 23 September 2026.
Tycon Systems has released firmware 2.4.5, which resolves this vulnerability by requiring an administrator username and password to be set before the web interface is served. Further inquiries can be directed to security@tyconsystems.com.
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 9.8, EPSS 0.4%, industrial relevance 40/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Possible loss of visibility of or control over the process upon successful exploitation.
No strong energy-sector-specific signals recognised; general OT/ICS relevance.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 24 September 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.