Loading vulnerabilities…
Loading vulnerabilities…
CVE-2026-62647
A vulnerability has been identified in Reyrolle 7SR5 (All versions < V2.70). A random number generator is used to generate security-relevant values (such as session identifiers used for authentication purposes) that is not initialized with a True Random Number Generator (TRNG), resulting in a predictable sequence of generated values. This could allow an unauthenticated remote attacker to more easily predict the generated values and impersonate a legitimate authenticated user, potentially gaining unauthorized access to the device.
This record: live connection— last retrieved: 24 September 2026 at 05:13.
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
A vulnerability has been identified in Reyrolle 7SR5 (All versions < V2.70). A random number generator is used to generate security-relevant values (such as session identifiers used for authentication purposes) that is not initialized with a True Random Number Generator (TRNG), resulting in a predictable sequence of generated values. This could allow an unauthenticated remote attacker to more easily predict the generated values and impersonate a legitimate authenticated user, potentially gaining unauthorized access to the device.
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
High
Integrity
High
Availability
None
Probability of exploitation within 30 days
0.3%
Percentile
27e
Source: FIRST.org, updated on 23 September 2026.
Update to V2.70 or later version
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 7.4, EPSS 0.3%, industrial relevance 55/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Limited impact on availability; the risk lies mainly with confidentiality or integrity of process data.
Assessed as relevant to the energy sector based on: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Vendor "Siemens" is a known supplier of equipment for the energy sector. Sector indication recognised in the description: energieopwekking.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 24 September 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.