CVE-2026-66369
The GOOSE parser contains an off-by-one boundary-handling flaw that can be triggered by a single unauthenticated Layer-2 multicast frame on the process bus. When specific GOOSE message fields are processed, the parser advances its internal buffer position incorrectly, resulting in a heap out-of-bounds read. On affected platforms, this condition reliably terminates the subscriber process and causes a denial-of-service.
This record: live connection— last retrieved: 24 September 2026 at 05:13.
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
The GOOSE parser contains an off-by-one boundary-handling flaw that can be triggered by a single unauthenticated Layer-2 multicast frame on the process bus. When specific GOOSE message fields are processed, the parser advances its internal buffer position incorrectly, resulting in a heap out-of-bounds read. On affected platforms, this condition reliably terminates the subscriber process and causes a denial-of-service.
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
None
Integrity
None
Availability
High
Probability of exploitation within 30 days
0.2%
Percentile
7e
Source: FIRST.org, updated on 23 September 2026.
MZ Automation GmbH recommends that users update to version 1.6.2.
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 6.5, EPSS 0.2%, industrial relevance 55/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Possible loss of visibility of or control over the process upon successful exploitation.
Assessed as relevant to the energy sector based on: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Beschrijving noemt een industrieel protocol dat typisch is voor elektriciteitsnetten (iec61850, goose).
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 24 September 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.