Loading vulnerabilities…
Loading vulnerabilities…
CVE-2026-78354
Missing release of resource after effective lifetime vulnerability in ABB System 800xA Batch Management. This issue affects System 800xA Batch Management: 7.0, 6.2, 6.1.1, and 6.0.3.4.
This record: live connection— last retrieved: 25 November 2026 at 00:04.
Vendor
Published
24 November 2026
Last modified
24 November 2026
Assessment
Medium49/100Industrial relevance
Medium55/100Confidence
MediumPriority 49/100: relevant, but less urgent than the highest-priority vulnerabilities.
Based on CVSS 4.3, no EPSS score available, industrial relevance 55/100.
No confirmed exploitation known: not on the CISA KEV list.
No EPSS score available yet.
Sources
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
Missing release of resource after effective lifetime vulnerability in ABB System 800xA Batch Management. This issue affects System 800xA Batch Management: 7.0, 6.2, 6.1.1, and 6.0.3.4.
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
None
Integrity
None
Availability
Limited
No EPSS score available at the time of retrieval (e.g. for a very recent CVE).
Workarounds are specific measures that a user can take to help block an attack, for example, temporarily disabling the vulnerable feature may remove the exposure with well-known impact on functionality. ABB has tested the following workarounds. Although these workarounds will not correct the underlying vulnerability, they can help block known attack vectors. When a workaround reduces functionality, this is identified below as “Impact of workaround”. ABB has identified the following workarounds that can reduce exposure: - Network Segmentation: Restrict access to systems running 800xA Batch Management through firewalls and industrial network segmentation. - Access Control: Allow TCP connections to port 40061/TCP only from authorized systems and trusted communication partners. - Monitoring: Monitor systems for abnormal connection volumes and investigate excessive TCP connection attempts. Impact of Workaround: No loss of system functionality is expected when standard industrial network security practices are implemented.
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 4.3, no EPSS score available, industrial relevance 55/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Limited impact on availability; the risk lies mainly with confidentiality or integrity of process data.
Assessed as relevant to the energy sector based on: Vermeld in een officiële ICS-advisory (van CISA of de leverancier), wat directe relevantie voor industriële besturingssystemen bevestigt. Vendor "ABB" is a known supplier of equipment for the energy sector.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 25 November 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.