CVE-2026-8173
The web GUI of affected Murrelektronik Xelity switches logs MAC addresses from the devices MAC address table when an authenticated administrator uses the 'Copy learned MAC Addresses' function. Due to improper generation of error messages, an unauthenticated attacker with network access to the web interface can retrieve the logged MAC addresses via browser developer tools.
This record: live connection— last retrieved: 7 November 2026 at 14:22.
Vendor
Published
24 August 2026
Last modified
14 October 2026
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
The web GUI of affected Murrelektronik Xelity switches logs MAC addresses from the devices MAC address table when an authenticated administrator uses the 'Copy learned MAC Addresses' function. Due to improper generation of error messages, an unauthenticated attacker with network access to the web interface can retrieve the logged MAC addresses via browser developer tools.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
Limited
Integrity
None
Availability
None
Probability of exploitation within 30 days
0.3%
Percentile
28e
Source: FIRST.org, updated on 6 November 2026.
Update the affected Xelity switches to firmware version V2.1.1 or later. This firmware version removes the syslog error that caused the MAC address table contents to be written to a web-accessible log.
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 5.3, EPSS 0.3%, industrial relevance 45/100; raised due to relevance to internet exposure.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Limited impact on availability; the risk lies mainly with confidentiality or integrity of process data.
No strong energy-sector-specific signals recognised; general OT/ICS relevance.
This product uses protocols that are relevant to internet exposure analysis. An internet-reachable service is not automatically vulnerable.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 7 November 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.