CVE-2026-9636
A security issue exists within CompactLogix® 5380, ControlLogix® 5580, and EN4 communication modules related to CIP Security certificate revocation handling. The security issue stems from the controller failing to properly reject certificates signed by an intermediate certificate that has been revoked via a Certificate Revocation List (CRL). This could allow a network-based attacker to establish a connection using a certificate that should be untrusted, potentially bypassing CIP Security protections.
This record: live connection— last retrieved: 24 September 2026 at 05:11.
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
A security issue exists within CompactLogix® 5380, ControlLogix® 5580, and EN4 communication modules related to CIP Security certificate revocation handling. The security issue stems from the controller failing to properly reject certificates signed by an intermediate certificate that has been revoked via a Certificate Revocation List (CRL). This could allow a network-based attacker to establish a connection using a certificate that should be untrusted, potentially bypassing CIP Security protections.
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
None
Integrity
None
Availability
None
Probability of exploitation within 30 days
0.2%
Percentile
12e
Source: FIRST.org, updated on 23 September 2026.
Rockwell Automation recommend users update to the following versions: ControlLogix 5580: Update to V38.011
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 5.9, EPSS 0.2%, industrial relevance 55/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Limited impact on availability; the risk lies mainly with confidentiality or integrity of process data.
Assessed as relevant to the energy sector based on: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Vendor "Rockwell Automation" is a known supplier of equipment for the energy sector.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 24 September 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.