CISA + Hersteller
ICS-Advisories
Advisories speziell für industrielle Steuerungssysteme — von CISA ICS-CERT und direkt von Herstellern (darunter Siemens, ABB, Schneider Electric, WAGO und Phoenix Contact) — einschließlich Revisionshistorie (Erstveröffentlichung, Update A, Update B) und verknüpfter CVEs.
1
Gefunden
Advisory-Daten: Live-Anbindung— zuletzt abgerufen: 7. November 2026 um 02:35.
Filter
1 aktiv1 Advisories gefunden
VDE-2021-033
TRUMPF Laser GmbH: multiple products prone to codesys runtime vulnerabilities
Veröffentlicht
12. August 2021
Letzte Aktualisierung
12. August 2021
Verknüpfte CVEs
Betroffene Sektoren
Risk Evaluation
The TruControl laser control software (versions 1.04 to 3.0.0) uses CODESYS runtime versions affected by multiple CVEs: **CVE list:** - CVE-2021-29242 - CVE-2021-29241 - CVE-2019-5105 - CVE-2020-7052 - CVE-2019-9012 - CVE-2019-9010 - CVE-2019-9009 - CVE-2018-10612 In addition to the CVEs listed above, the affected products are also vulnerable to the following issues without a CVE ID: --- ### **CODESYS Advisory 2018-07** A crafted communication request may cause an access violation in the affected CODESYS products and may result in a denial-of-service condition. - **CVSS v3.0 base score:** 6.5 - **CVSS v3.0 vector:** `CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H` 🔗 [Link to advisory](https://customers.codesys.com/index.php?eID=dumpFile&t=f&f=12928&token=6d1dcea05a15aeef7ad48eadc64c8eca5d4f07b2&download=) --- ### **CODESYS Advisory 2018-04** The CODESYS runtime system allows access to files outside the restricted working directory of the controller by online services. - **CVSS v3.0 base score:** 9.9 - **CVSS v3.0 vector:** `CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H` 🔗 [Link to advisory](https://customers.codesys.com/index.php?eID=dumpFile&t=f&f=12925&token=50e7240fa947ea215311e3db441f82152f1109b6&download=) --- ### **CODESYS Advisory 2017-03** A crafted request may cause an access violation in the affected CODESYS products and may result in a denial-of-service condition. - **CVSS v3.0 base score:** 7.5 - **CVSS v3.0 vector:** `CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H` 🔗 [Link to advisory](https://customers.codesys.com/index.php?eID=dumpFile&t=f&f=12912&token=2f23e7f047c2768dd06fdf072de49a7ba1fe9687&download=)
Zusammenfassung der Gegenmaßnahmen
- We highly recommend updating to TruControl version 3.16.0 or higher as soon as possible - Please contact your service partner (service.tls@trumpf.com) for immediate instructions on how to retrieve the update
Revisionshistorie (1)
Erstveröffentlichung — 12. August 2021
initial revision