Schwachstellen werden geladen…
Schwachstellen werden geladen…
CVE-2019-5105
An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).
Dieser Datensatz: Live-Anbindung— zuletzt abgerufen: 7. November 2026 um 02:05.
Produkte
PMC programming tool 3.x.x, CODESYS Development System, Automation Suite, Controller CECC-D, Controller CECC-LK, Controller CECC-S und 6 weitere
bis Version 3.0.0<=3.5.15
Veröffentlicht
26. März 2020
Zuletzt geändert
17. Juni 2026
Direkt aus NVD, CISA oder vom Hersteller übernommen — teils auf Englisch, unverändert gegenüber der Quelle.
An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack Vector
NETWORK
Privileges Required
NONE
User Interaction
NONE
Vertraulichkeit
Keine
Integrität
Keine
Verfügbarkeit
Hoch
Ausnutzungswahrscheinlichkeit innerhalb von 30 Tagen
2.6%
Perzentil
86e
Quelle: FIRST.org, aktualisiert am 6. November 2026.
Use a hardware firewall, host-based firewall or comparable measures at network level toprotect against unauthorised network communication with the PC. Use a virus scanner or other measures to protect against malware. Only use CODESYS libraries and archives from trusted sources.
Unsere eigene Einordnung und unser Kontext zu den obigen Quelldaten.
IACS-Radar-Einordnung
Unsere eigene Einordnung und unser Kontext zu dieser Schwachstelle — keine offizielle Quelle.
IACS-Radar-Prioritätswert
Basierend auf CVSS 7.5, EPSS 2.6%, industrielle Relevanz 60/100.
Kombiniert CVSS, EPSS, KEV-Status, industrielle Relevanz und Expositionsrelevanz — eine Ergänzung, kein Ersatz für die einzelnen Werte darunter und darüber.
Voraussetzungen für eine Ausnutzung
Operative Auswirkungen & Energierelevanz
Möglicher Verlust der Sicht auf oder der Kontrolle über den Prozess bei erfolgreicher Ausnutzung.
Als relevant für den Energiesektor eingestuft aufgrund von: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Productbeschrijving komt overeen met de categorie "HMI", een typisch OT/ICS-componenttype.
Empfohlene defensive Maßnahmen
Industrieller Relevanzwert
Automatisch als industriell relevant eingestuft anhand von CISA-/NVD-Signalen (siehe Gründe).
Klassifiziert von IACS Radar-analysepijplijn (geautomatiseerd) am 7. November 2026.
IEC-62443-Zuordnung
Automatische IACS-Radar-Einordnung anhand der gemeldeten CWE-Schwächeklassifizierung; keine offizielle Zertifizierungsaussage.