CISA + vendors
ICS Advisories
Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.
1
Found
Advisory data: live connection— last retrieved: 8 November 2026 at 10:21.
Filters
1 active1 advisories found
3ADR011572
Automation Builder, Drive Application Builder, Virtual Drive, Virtual DrivePlus Impacted by multiple vulnerabilities in Wibu CodeMeter
Published
3 September 2026
Last update
3 September 2026
Affected sectors
Risk evaluation
An update is available that resolves publicly reported vulnerabilities in the product versions listed as affected in the advisory. An attacker who successfully exploited these vulnerabilities could - allow arbitrary files to be deleted with system privileges (CVE-2026-81572), - read potentially sensitive configuration data and overwrite selected values in Server.ini (CVE-2026-81573), - crash CodeMeter and disclose sensitive information such as process memory and stack canaries (CVE-2026-81574), - crash CodeMeter (CVE-2026-81575), or - read potentially sensitive license information (CVE-2026-81576)
Mitigation summary
For CVE-2026-81572 the exposure can be limited by auditing the list of local users and removing any unnecessary accounts. For CVE-2026-81573, CVE-2026-81574, CVE-2026-81575, and CVE-2026-81576: If you enabled the network server functionality at some point but no longer need it, disable it: - Open the Registry Editor and navigate to Computer\HKEY_LOCAL_MACHINE\SOFTWARE\ WIBUSYSTEMS\CodeMeter\Server\CurrentVersion\, then change the value of IsNetworkServerfrom 1 to 0. - Restart CodeMeter.
Revision history (1)
Initial publication — 3 September 2026
Initial version.