Skip to content
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + vendors

ICS Advisories

Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.

1

Found

Advisory data: live connection— last retrieved: 8 November 2026 at 10:21.

Filters

1 active
Reset filters

1 advisories found

3BHS973333

AC 800PEC, AC 800PEC ARM, AC 800PEC Tool, Control Terminal (xCT) and AC 800PEC Tool Cheetah Impacted by multiple vulnerabilities in Wibu CodeMeter

ABB — AC 800PEC

ABB PSIRThigh

Published

10 September 2026

Last update

10 September 2026

Affected sectors

Risk evaluation

An update is available that resolves a publicly reported vulnerability in the product versions listed as affected in the advisory. An attacker who successfully exploited these vulnerabilities could - Allow arbitrary files to be deleted with system privileges (CVE-2026-81572), - Read potentially sensitive configuration data and overwrite selected values in Server.ini (CVE-2026-81573) - Crash CodeMeter and disclose sensitive information such as process memory and stack canar-ies (CVE-2026-81574) - Crash CodeMeter (CVE-2026-81575), or - Read potentially sensitive license information (CVE-2026-81576)

Mitigation summary

For CVE-2026-81573, CVE-2026-81574, CVE-2026-81575, and CVE-2026-81576: If you enabled the network server functionality at some point but no longer need it, disable it: - Open the Registry Editor and navigate to Computer\HKEY_LOCAL_MACHINE\SOFTWARE\ WIBUSYSTEMS\CodeMeter\Server\CurrentVersion\, then change the value of IsNetworkServerfrom 1 to 0. - Restart CodeMeter.

Revision history (1)
  1. Initial publication — 10 September 2026

    Initial version.

Official source: ABB PSIRT