Skip to content
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + vendors

ICS Advisories

Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.

1

Found

Advisory data: live connection— last retrieved: 8 November 2026 at 10:21.

Filters

1 active
Reset filters

1 advisories found

ICSA-26-218-01

ABB Ability Zenon

ABB — Ability Zenon

CISAhigh

Published

30 July 2026

Last update

6 August 2026

Affected sectors

Risk evaluation

ABB is aware of publicly reported vulnerabilities affecting MongoDB 4.2, which is bundled within the IIoT Services of the affected product versions. MongoDB 4.2 has reached end-of-life and contains multiple known security vulnerabilities. An attacker who successfully exploits these vulnerabilities could potentially access sensitive information, cause denial of service, or disrupt system availability.

Mitigation summary

ABB recommends the following mitigation measures: - Replace bundled MongoDB with a supported version if IIoT services are required: - Where IIoT functionality is required, the bundled MongoDB instance can be replaced with a supported and patched version through manual configuration. - The following zenon online help section explains the process of installing and using your own MongoDB database: zenHelpViewer - Uninstall IIoT Services wherever it’s not required: - If IIoT Services are not required, they can be removed using the Control panel uninstaller. This eliminates the dependency on MongoDB without affecting other zenon components. Refer to section “General security recommendations” for further advise on how to keep your system secure.

Revision history (2)
  1. Initial publication — 30 July 2026

    Initial version

  2. Update A — 6 August 2026

    Initial CISA Republication of ABB PSIRT 9AKK108472A9037 advisory

Official source: CISA