CISA + vendors
ICS Advisories
Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.
1
Found
Advisory data: live connection— last retrieved: 20 November 2026 at 20:17.
Filters
1 active1 advisories found
Published
14 February 2025
Last update
13 November 2026
Linked CVEs
Affected sectors
Risk evaluation
SICK has identified vulnerabilities in MEAC300. These vulnerabilities, related to the OpenSSL library and specific device functionalities, could potentially allow remote, unauthenticated attackers to: 1) Cause a denial of service: Triggering an infinite loop that consumes CPU resources, rendering the device unresponsive (CVE-2022-0778). This impacts MEAC300 DE devices running vulnerable OpenSSL versions when processing manipulated SSH certificates. 2) Compromise the MEAC300: Exploit vulnerabilities accessible via Ethernet to potentially impact the availability, integrity, and confidentiality of the device. SICK recommends ensuring that affected products operate within secure network environments to mitigate these risks.
Mitigation summary
Users are strongly recommended to upgrade to the latest release of the MEAC300 (>=4.0.54.21) that includes a patch for the vulnerability.
Revision history (4)
Initial publication — 14 February 2025
Initial version
Update A — 21 February 2025
Fix provided for CVE-2025-0867
Update B — 30 July 2025
Updated Advisory: URL for SICK Operating Guidelines has been updated
Update C — 13 November 2026
Corrected initial_release_date to match the date of the initial revision (revision 1). No changes to vulnerability, product, or remediation information.