CVE-2025-0867
The standard user uses the run as function to start the MEAC applications with administrative privileges. To ensure that the system can startup on its own, the credentials of the administrator were stored. Consequently, the EPC2 user can execute any command with administrative privileges. This allows a privilege escalation to the administrative level.
This record: live connection— last retrieved: 20 November 2026 at 19:46.
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
The standard user uses the run as function to start the MEAC applications with administrative privileges. To ensure that the system can startup on its own, the credentials of the administrator were stored. Consequently, the EPC2 user can execute any command with administrative privileges. This allows a privilege escalation to the administrative level.
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H
Attack vector
NETWORK
Privileges required
LOW
User interaction
NONE
Confidentiality
High
Integrity
High
Availability
High
Probability of exploitation within 30 days
0.6%
Percentile
51e
Source: FIRST.org, updated on 20 November 2026.
Users are strongly recommended to upgrade to the latest release of the MEAC300 (>=4.0.54.21) that includes a patch for the vulnerability.
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 9.9, EPSS 0.6%, industrial relevance 40/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Possible loss of visibility of or control over the process upon successful exploitation.
No strong energy-sector-specific signals recognised; general OT/ICS relevance.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 20 November 2026.
IEC 62443 mapping