VDE-2021-051
Beckhoff: Relative path traversal vulnerability through TwinCAT OPC UA Server
Risk evaluation
Through specific nodes of the server configuration interface of the TwinCAT OPC UA Server administrators are able to remotely create and delete any files on the system which the server is running on, though this access should have been restricted to specific directories. In case that configuration interface is combined with not recommended settings to allow anonymous access via the TwinCAT OPC UA Server then this kind of file access is even possible for any unauthenticated user from remote.
Mitigation summary
Consider restricting access to the nodes of the 'TcOpcUAServer' with the methods described by https://infosys.beckhoff.com/content/1033/tcopcuaserver/5930038411-1.html such that the administrative interface can only be accessed by administrative users of well known OPC UA clients.
Revision history (2)
Initial publication — 4 November 2021
initial revision
Update A — 22 May 2025
Fix: added distribution, quotation mark