VDE-2021-051

Beckhoff: Relative path traversal vulnerability through TwinCAT OPC UA Server

Beckhoff — TwinCAT OPC UA Server in TF6100 < 4.3.48.0

Beckhoff PSIRTmiddel

Published

4 November 2021

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

Through specific nodes of the server configuration interface of the TwinCAT OPC UA Server administrators are able to remotely create and delete any files on the system which the server is running on, though this access should have been restricted to specific directories. In case that configuration interface is combined with not recommended settings to allow anonymous access via the TwinCAT OPC UA Server then this kind of file access is even possible for any unauthenticated user from remote.

Mitigation summary

Consider restricting access to the nodes of the 'TcOpcUAServer' with the methods described by https://infosys.beckhoff.com/content/1033/tcopcuaserver/5930038411-1.html such that the administrative interface can only be accessed by administrative users of well known OPC UA clients.

Revision history (2)
  1. Initial publication — 4 November 2021

    initial revision

  2. Update A — 22 May 2025

    Fix: added distribution, quotation mark

Official source: Beckhoff PSIRT