CVE-2021-34594
TwinCAT OPC UA Server in TF6100 and TS6100 in product versions before 4.3.48.0 or with TcOpcUaServer versions below 3.2.0.194 are prone to a relative path traversal that allow administrators to create or delete any files on the system.
This record: live connection— last retrieved: 7 November 2026 at 14:22.
Vendor
Products
TwinCAT OPC UA Server in TF6100 < 4.3.48.0, TwinCAT OPC UA Server in TS6100 < 4.3.48.0
up to version <3.2.0.194
Published
4 November 2021
Last modified
17 June 2026
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
TwinCAT OPC UA Server in TF6100 and TS6100 in product versions before 4.3.48.0 or with TcOpcUaServer versions below 3.2.0.194 are prone to a relative path traversal that allow administrators to create or delete any files on the system.
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H
Attack vector
NETWORK
Privileges required
HIGH
User interaction
NONE
Confidentiality
None
Integrity
High
Availability
High
Probability of exploitation within 30 days
1.1%
Percentile
66e
Source: FIRST.org, updated on 6 November 2026.
Consider restricting access to the nodes of the 'TcOpcUAServer' with the methods described by https://infosys.beckhoff.com/content/1033/tcopcuaserver/5930038411-1.html such that the administrative interface can only be accessed by administrative users of well known OPC UA clients.
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 6.5, EPSS 1.1%, industrial relevance 80/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Possible loss of visibility of or control over the process upon successful exploitation.
Assessed as relevant to the energy sector based on: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Productbeschrijving komt overeen met de categorie "opc-server", een typisch OT/ICS-componenttype. Vendor "Beckhoff" is a known supplier of equipment for the energy sector. Description mentions industrial protocol: opc-ua.
Recommended defensive measures
Industrial relevance score
Automatically classified as industrially relevant based on CISA/NVD signals (see reasons).
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 7 November 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.