Skip to content
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + vendors

ICS Advisories

Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.

1

Found

Advisory data: live connection— last retrieved: 7 November 2026 at 01:04.

Filters

1 active
Reset filters

1 advisories found

VDE-2025-080

WAGO: Multiple Vulnerabilities in I/O-Check Service

WAGO — CC100

WAGO PSIRTcritical

Published

9 September 2025

Last update

9 September 2025

Linked CVEs

Affected sectors

Risk evaluation

A missing authentication vulnerability exists in the iocheckd service "I/O-Check" functionality. A single packet can cause a denial of service and weaken credentials resulting in the default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.

Mitigation summary

The I/O-Check service protocol is only needed during installation and commissioning, not during normal operations. It is highly recommended to disable the IP-port 6626 after commissioning.

Revision history (1)
  1. Initial publication — 9 September 2025

    Initial revision.

Official source: WAGO PSIRT