CVE-2019-5080
An exploitable denial-of-service vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC 200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A single packet can cause a denial of service and weaken credentials resulting in the default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.
This record: live connection— last retrieved: 7 November 2026 at 01:04.
Vendor
Products
CC100, PFC100, PFC200, Basic Controller 100, TP600, Edge Controller and 2 more
up to version vers:all/*
Published
18 December 2019
Last modified
17 June 2026
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
An exploitable denial-of-service vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC 200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A single packet can cause a denial of service and weaken credentials resulting in the default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
None
Integrity
High
Availability
High
Probability of exploitation within 30 days
1.9%
Percentile
79e
Source: FIRST.org, updated on 6 November 2026.
The I/O-Check service protocol is only needed during installation and commissioning, not during normal operations. It is highly recommended to disable the IP-port 6626 after commissioning.
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 9.1, EPSS 1.9%, industrial relevance 55/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Possible loss of visibility of or control over the process upon successful exploitation.
Assessed as relevant to the energy sector based on: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Vendor "WAGO" is a known supplier of equipment for the energy sector.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 7 November 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.