CVE-2018-7849
A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum and Modicon Premium which could cause a possible Denial of Service due to improper data integrity check when sending files the controller over Modbus.
This record: live connection— last retrieved: 7 November 2026 at 14:22.
Vendor
Products
Modicon, Modicon Momentum Unity M1E Processor (part numbers 171CBU*) Controller, Modicon Quantum Controller, Modicon Quantum Safety Controller, Modicon Premium Controller, EcoStruxure Control Expert
up to version vers:intdot/<2.90
Published
22 May 2019
Last modified
17 June 2026
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum and Modicon Premium which could cause a possible Denial of Service due to improper data integrity check when sending files the controller over Modbus.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
None
Integrity
None
Availability
High
Probability of exploitation within 30 days
3.2%
Percentile
88e
Source: FIRST.org, updated on 6 November 2026.
Version sv4.20 of Modicon M580 includes a fix for this vulnerability and is available for download here: STEP 1: Update software and firmware. • On the engineering workstation, update to EcoStruxure Control Expert v16.0: https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/#software-and-firmware • On the Modicon M580 controller, update to firmware SV4.20 or above: https://www.se.com/ww/en/product-range/62098-modicon-m580-epac/#software-and-firmware STEP 2: Update projects in EcoStruxure™ Control Expert by: • Setting up an application password in the project properties • Changing the version of the controller firmware to match the new firmware version of the target controller STEP 3: Rebuild and transfer projects in EcoStruxure™ Control Expert: • Rebuild all current projects
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 7.5, EPSS 3.2%, industrial relevance 60/100; raised due to relevance to internet exposure.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Possible loss of visibility of or control over the process upon successful exploitation.
Assessed as relevant to the energy sector based on: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Vendor "Schneider Electric" is a known supplier of equipment for the energy sector. Description mentions industrial protocol: modbus-tcp.
This product uses protocols that are relevant to internet exposure analysis. An internet-reachable service is not automatically vulnerable.
Recommended defensive measures