Loading vulnerabilities…
Loading vulnerabilities…
CVE-2018-7850
A CWE-807: Reliance on Untrusted Inputs in a Security Decision vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause invalid information displayed in Unity Pro software.
This record: live connection— last retrieved: 7 November 2026 at 14:22.
Vendor
Products
Modicon, Modicon Momentum Unity M1E Processor (part numbers 171CBU*) Controller, Modicon Quantum Controller, Modicon Quantum Safety Controller, Modicon Premium Controller, EcoStruxure Control Expert
up to version vers:intdot/<2.90
Published
22 May 2019
Last modified
17 June 2026
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
A CWE-807: Reliance on Untrusted Inputs in a Security Decision vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause invalid information displayed in Unity Pro software.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Confidentiality
Limited
Integrity
None
Availability
None
Probability of exploitation within 30 days
1.5%
Percentile
75e
Source: FIRST.org, updated on 6 November 2026.
Version sv4.20 of Modicon M580 includes a fix for this vulnerability and is available for download here: STEP 1: Update software and firmware. • On the engineering workstation, update to EcoStruxure Control Expert v16.0: https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/#software-and-firmware • On the Modicon M580 controller, update to firmware SV4.20 or above: https://www.se.com/ww/en/product-range/62098-modicon-m580-epac/#software-and-firmware STEP 2: Update projects in EcoStruxure™ Control Expert by: • Setting up an application password in the project properties • Changing the version of the controller firmware to match the new firmware version of the target controller STEP 3: Rebuild and transfer projects in EcoStruxure™ Control Expert: • Rebuild all current projects
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 5.3, EPSS 1.5%, industrial relevance 55/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Limited impact on availability; the risk lies mainly with confidentiality or integrity of process data.
Assessed as relevant to the energy sector based on: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Vendor "Schneider Electric" is a known supplier of equipment for the energy sector.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 7 November 2026.
IEC 62443 mapping
Automatic IACS Radar assessment based on the reported CWE weakness classification; not an official certification statement.