Loading vulnerabilities…
Loading vulnerabilities…
CVE-2025-36558
KUNBUS PiCtory version 2.11.1 and earlier are vulnerable to a cross-site-scripting attack via the sso_token used for authentication. If an attacker provides the user with a PiCtory URL containing an HTML script as an sso_token, that script will reply to the user and be executed.
This record: live connection— last retrieved: 7 November 2026 at 17:25.
Taken directly from NVD, CISA or the vendor — sometimes in English, unchanged from the source.
KUNBUS PiCtory version 2.11.1 and earlier are vulnerable to a cross-site-scripting attack via the sso_token used for authentication. If an attacker provides the user with a PiCtory URL containing an HTML script as an sso_token, that script will reply to the user and be executed.
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N
Attack vector
NETWORK
Privileges required
NONE
User interaction
REQUIRED
Confidentiality
Limited
Integrity
Limited
Availability
None
Probability of exploitation within 30 days
21.1%
Percentile
98e
Source: FIRST.org, updated on 6 November 2026.
Update the PiCtory package to version 2.12 via the 'apt' package manager. Use 'sudo apt update && sudo apt upgrade -y' to pull and install all available updates for the IndustrialPI. To check the version of the pictory package, use 'dpkg -l | grep pictory'.
Our own interpretation and context for the source data above.
IACS Radar assessment
Our own interpretation and context for this vulnerability — not an official source.
IACS Radar priority score
Based on CVSS 6.1, EPSS 21.1%, industrial relevance 40/100.
Combines CVSS, EPSS, KEV status, industrial relevance and exposure relevance — a complement to, not a replacement for, the individual scores below and above.
Conditions for exploitation
Operational impact & energy relevance
Limited impact on availability; the risk lies mainly with confidentiality or integrity of process data.
No strong energy-sector-specific signals recognised; general OT/ICS relevance.
Recommended defensive measures
Industrial relevance score
Classification is provisional; manual verification by an OT security analyst is recommended.
Classified by IACS Radar-analysepijplijn (geautomatiseerd) on 7 November 2026.
IEC 62443 mapping